Customized Electrolyte Cooling System for Lead-Acid Battery Production
Project Background: An Indian lead-acid battery manufacturer needed to cool sulfuric acid electrolyte with a concentration of 70–90% to -5°C. Due to the highly corrosive nature of the electrolyte, it could not be circulated directly through a conventional industrial chiller.
The customer needed a solution that could maintain stable low temperatures under varying production loads, safely circulate the concentrated acid, and integrate with the existing battery production line.
KANSA designed a customized indirect cooling system that separates the corrosive electrolyte from the chiller's coolant circuit while allowing heat transfer between the two.
- ICA-5M Air-Cooled Industrial Chiller: Provides 7 kW of cooling capacity with an operating temperature of -5°C.
- Hastelloy Plate Heat Exchanger: Transfers heat between the sulfuric acid and chiller coolant circuits while keeping the two fluids separate.
- Acid-Resistant Pump: Circulates the concentrated sulfuric acid through the acid-side circuit.
- Stainless Steel Centrifugal Pump: Circulates the coolant through the chiller-side circuit.
To accommodate changes in production load, the ICA-5M chiller uses a control system with sensors that automatically adjust cooling operation to maintain temperature stability within ±0.5°C.
KANSA also customized the piping arrangement, pump flow rates, and system layout to accommodate the available installation space and connect with the customer's existing production line, while allowing for future expansion.
The completed system maintained the electrolyte temperature at -5°C while keeping the corrosive sulfuric acid isolated from the chiller's circulation circuit.
By integrating the industrial chiller, Hastelloy plate heat exchanger, and dedicated circulation pumps, KANSA provided the low-temperature cooling required for the customer's lead-acid battery production process.